smoke exhaust system

smoke exhaust system

A mechanical or gravity system intended to convey smoke from one portion of a building to the outdoors; usually includes a purging-and-venting system, as well as exhaust fans.
Mentioned in ?
References in periodicals archive ?
the choice of a contractor to carry out design and construction works at the construction site overhaul of the smoke exhaust system of residential buildings located at: borisov, serebrennikova st.
This requirement is typically met in an indoor facility by providing a smoke exhaust system.
The current restriction defined by NFPA 92 states that makeup air must not exceed 1.02 m/s (200 fpm) during the operation of a mechanical smoke exhaust system (NFPA 2015).
If a fire or smoke damper placement will interfere with the operation of an engineered smoke exhaust system (such as for an atrium), approved alternate protection shall be used (IBC [paragraph] 717.2.1).
For example, the fire marshal has continued testing the building's smoke exhaust system. Although some issues have arisen during this testing, such as the potential need for additional or larger smoke exhaust fans for a portion of the building, no new significant issues have emerged.
The infrastructure supports a flexible lab design, an innovative smoke exhaust system in the main atrium and a heat recovery system for energy savings.
"This is particularly common in storage occupancies (from stacking a few boxes of metal containers at a 4-foot height to assembling large storage racks that hold hazardous, combustible objects) and atriums (where a change in use of the space may affect the smoke exhaust system that has been designed for a minimal hazard)."
Compile a list of switches that control smoke exhaust, and mark them on a floor plan labeled "Smoke Exhaust." Note whether the smoke exhaust system is connected to the fire alarm system and is automatically operated when the fire alarm system is activated.
Such relocation of ceiling tiles could have an adverse impact on the performance of the smoke exhaust system. The effort involved with periodic testing of such a smoke exhaust system can be significantly increased due to the need for repair of suspended ceilings after testing.
* A smoke exhaust system to purge the building of smoke in the case of fire.
Section A.10.1.1 of NFPA 204 suggests that for smoke layer temperature differences below 110[degrees]C (230[degrees]F) a powered smoke exhaust system may need to be considered, as per NFPA 92B (2009).